{"id":4338,"date":"2026-10-22T15:54:00","date_gmt":"2026-10-22T15:54:00","guid":{"rendered":"https:\/\/www.savioclima.com\/?p=4338"},"modified":"2026-10-23T09:21:29","modified_gmt":"2026-10-23T09:21:29","slug":"genset-radiator-fan-sizing","status":"publish","type":"post","link":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/","title":{"rendered":"Genset Radiator Fans: How to Size Airflow and Static Pressure"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">A generator set is only as reliable as its cooling system. If the radiator fans move too little air at the hottest hour of the year, the engine derates or shuts down, exactly when the standby power is needed. This guide shows how to size <strong>genset radiator fans<\/strong> in US units: the airflow you need, the static pressure the fans must overcome, and what changes when the fans run on 60 Hz.<\/p>\n\n<h2 class=\"wp-block-heading\">1. Start from the heat rejection<\/h2>\n\n<p class=\"wp-block-paragraph\">Everything begins with the heat the cooling package must reject to air. The engine manufacturer gives it on the data sheet, usually split into two circuits:<\/p>\n\n<ul class=\"wp-block-list\">\n<li><strong>Jacket water<\/strong> (high-temperature circuit), the heat removed from the engine block and cylinder heads<\/li>\n\n<li><strong>Charge-air cooler or aftercooler<\/strong> (low-temperature circuit), the heat removed from the compressed combustion air on turbocharged engines<\/li>\n<\/ul>\n\n<p class=\"wp-block-paragraph\">Add the circuits that share the same radiator and fans. Use the value at <strong>full load and maximum ambient<\/strong>, not the nominal figure, and convert it to BTU\/hr: 1 kW = 3,412 BTU\/hr.<\/p>\n\n<h2 class=\"wp-block-heading\">2. Calculate the airflow<\/h2>\n\n<p class=\"wp-block-paragraph\">The airflow follows from an energy balance on the air side. For air at standard density (0.075 lb\/ft\u00b3, 70 \u00b0F, sea level):<\/p>\n\n<p class=\"has-background wp-block-paragraph\" style=\"background-color:#EEF4F8;padding-top:14px;padding-right:20px;padding-bottom:14px;padding-left:20px\"><code>CFM = Heat rejection (BTU\/hr) \u00f7 (1.08 \u00d7 \u0394T)<\/code><\/p>\n\n<p class=\"wp-block-paragraph\">Here <strong>\u0394T<\/strong> is the air temperature rise across the radiator in \u00b0F, and 1.08 = 60 min\/hr \u00d7 0.075 lb\/ft\u00b3 \u00d7 0.24 BTU\/lb\u00b7\u00b0F. The radiator maker sets \u0394T together with the core size: a smaller \u0394T means a bigger core and more air, a larger \u0394T means a smaller core but hotter coolant.<\/p>\n\n<h3 class=\"wp-block-heading\">Correct for temperature and altitude<\/h3>\n\n<p class=\"wp-block-paragraph\">Fans move volume, but air carries heat by mass. On a hot day or at altitude each cubic foot weighs less, so you need more CFM to carry the same heat. Divide the standard CFM by the density ratio:<\/p>\n\n<p class=\"has-background wp-block-paragraph\" style=\"background-color:#EEF4F8;padding-top:14px;padding-right:20px;padding-bottom:14px;padding-left:20px\"><code>Density ratio = [530 \u00f7 (460 + T \u00b0F)] \u00d7 [barometric pressure \u00f7 29.92 in. Hg]<\/code><\/p>\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th>Condition<\/th><th>Density ratio<\/th><\/tr><\/thead><tbody><tr><td>70 \u00b0F, sea level<\/td><td>1.00<\/td><\/tr><tr><td>104 \u00b0F, sea level<\/td><td>0.94<\/td><\/tr><tr><td>122 \u00b0F, sea level<\/td><td>0.91<\/td><\/tr><tr><td>122 \u00b0F, 1,000 ft<\/td><td>0.88<\/td><\/tr><tr><td>122 \u00b0F, 5,000 ft<\/td><td>0.76<\/td><\/tr><\/tbody><\/table><\/figure>\n\n<h3 class=\"wp-block-heading\">Worked example<\/h3>\n\n<p class=\"wp-block-paragraph\">A natural gas generator set rejects <strong>900 kW<\/strong> through a combined jacket water and aftercooler radiator. The design air temperature rise is <strong>36 \u00b0F<\/strong>, the maximum ambient is <strong>122 \u00b0F<\/strong> and the site sits at <strong>1,000 ft<\/strong>.<\/p>\n\n<ol class=\"wp-block-list\">\n<li>Heat rejection: 900 kW \u00d7 3,412 = 3,070,800 BTU\/hr<\/li>\n\n<li>Standard airflow: 3,070,800 \u00f7 (1.08 \u00d7 36) \u2248 79,000 CFM<\/li>\n\n<li>Density correction: 79,000 \u00f7 0.88 \u2248 <strong>90,000 CFM<\/strong> at site conditions<\/li>\n\n<li>Fan arrangement: four fans of about 22,500 CFM each, plus a fifth as standby for N+1 redundancy<\/li>\n<\/ol>\n\n<h2 class=\"wp-block-heading\">3. Add up the static pressure<\/h2>\n\n<p class=\"wp-block-paragraph\">The fans must overcome every resistance in the air path. Ask each supplier for the pressure drop at the design airflow, then add them up:<\/p>\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th>Component<\/th><th>Typical range (in. w.g.)<\/th><\/tr><\/thead><tbody><tr><td>Radiator core<\/td><td>0.3 \u2013 0.8<\/td><\/tr><tr><td>Intake louvers, screens, filters<\/td><td>0.1 \u2013 0.3<\/td><\/tr><tr><td>Discharge damper, hood or duct<\/td><td>0.1 \u2013 0.4<\/td><\/tr><tr><td>Sound attenuators, if any<\/td><td>0.2 \u2013 0.5<\/td><\/tr><\/tbody><\/table><\/figure>\n\n<p class=\"wp-block-paragraph\">In the example, a core at 0.50 in. w.g., intake louvers at 0.20 and a discharge hood at 0.25 give <strong>0.95 in. w.g.<\/strong> Add a margin of 10 to 15% for fouling and installation effects, and select the fans for about <strong>1.05 in. w.g.<\/strong> at 22,500 CFM each. The ranges above are typical values only: always use the figures of your own components.<\/p>\n\n<p class=\"wp-block-paragraph\">Watch out for <strong>hot air recirculation<\/strong>. If discharge air finds its way back to the intake, the real inlet temperature rises and the whole calculation fails. Discharge and intake must be well separated, especially in enclosures and on rooftops.<\/p>\n\n<h2 class=\"wp-block-heading\">4. Pusher or puller, one fan or an array<\/h2>\n\n<ul class=\"wp-block-list\">\n<li><strong>Puller (draw-through):<\/strong> the fan sits downstream of the radiator and pulls air through it. The air reaching the core is more uniform, but the fan works in hot air.<\/li>\n\n<li><strong>Pusher (blow-through):<\/strong> the fan blows ambient air into the radiator. The fan and motor run cooler, which helps in high ambient sites.<\/li>\n\n<li><strong>Fan arrays:<\/strong> several smaller fans instead of one large fan allow N+1 redundancy, staging at part load and easier replacement. They suit data center gensets, where a single fan failure must not stop the unit. For high-resistance systems, see <a href=\"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/tubeaxial-vs-vaneaxial-vs-propeller-fans\/\">Tubeaxial vs Vaneaxial vs Propeller Fans<\/a>.<\/li>\n<\/ul>\n\n<h2 class=\"wp-block-heading\">5. What changes on 60 Hz<\/h2>\n\n<p class=\"wp-block-paragraph\">A fan selected on a 50 Hz curve does not behave the same on a 60 Hz supply. Motor speed rises by 20%, from about 1,450 to about 1,750 rpm for a 4-pole motor, and the fan laws do the rest:<\/p>\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th>Quantity<\/th><th>Fan law<\/th><th>50 Hz fan run at 60 Hz<\/th><\/tr><\/thead><tbody><tr><td>Airflow<\/td><td>\u221d speed<\/td><td>+20%<\/td><\/tr><tr><td>Static pressure<\/td><td>\u221d speed\u00b2<\/td><td>+44%<\/td><\/tr><tr><td>Power<\/td><td>\u221d speed\u00b3<\/td><td>+73%<\/td><\/tr><\/tbody><\/table><\/figure>\n\n<p class=\"wp-block-paragraph\">The extra power can overload the motor and overstress the impeller. That is why a fan for North America must be selected on <strong>60 Hz performance curves<\/strong>, with a motor sized for that speed, and not converted from a 50 Hz selection. More on this in <a href=\"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/50-hz-vs-60-hz-fans\/\">50 Hz vs 60 Hz Fans: What Changes When a Fan Runs in North America<\/a>.<\/p>\n\n<p class=\"wp-block-paragraph\">For the USA and Canada, also check the <strong>motor listing<\/strong> (UL or CSA), the supply voltage (460 V in the USA, 575 V in much of Canada), an IP55 \/ TEFC enclosure for outdoor duty, and inverter-duty insulation if the fans run on VFDs.<\/p>\n\n<h2 class=\"wp-block-heading\">6. Checklist: what to send your fan supplier<\/h2>\n\n<ul class=\"wp-block-list\">\n<li>Heat rejection per circuit, at full load and maximum ambient<\/li>\n\n<li>Maximum ambient temperature and site altitude<\/li>\n\n<li>Radiator core face area and pressure drop at design airflow<\/li>\n\n<li>Available space: maximum fan diameter and number of fans<\/li>\n\n<li>Arrangement: pusher or puller, horizontal or vertical discharge<\/li>\n\n<li>Supply: voltage, 60 Hz, VFD or direct-on-line<\/li>\n\n<li>Redundancy requirement (N+1) and noise limits at a given distance<\/li>\n\n<li>Hazardous area classification, if any<\/li>\n<\/ul>\n\n<h2 class=\"wp-block-heading\">SAVIO axial fans for genset cooling<\/h2>\n\n<p class=\"wp-block-paragraph\">SAVIO has built industrial axial fans in Italy since 1945. For genset radiators and charge-air coolers we offer <a href=\"https:\/\/www.savioclima.com\/en\/2023\/10\/23\/spm\/\">SPM<\/a> compact ducted fans (12&#8243; to 28&#8243;), <a href=\"https:\/\/www.savioclima.com\/en\/2023\/09\/21\/spmd-spmdr\/\">SPMD \/ SPMDR<\/a> double-bearing tubeaxial fans (31&#8243; to 63&#8243;) and <a href=\"https:\/\/www.savioclima.com\/en\/2023\/10\/23\/si-sir\/\">SI \/ SIR<\/a> adjustable-pitch fans, up to 88,000 CFM per unit. For North American projects we supply 60 Hz curves, UL \/ CSA motors at 460 V and 575 V, and performance verified in our in-house test room built to AMCA standards.<\/p>\n\n<p class=\"wp-block-paragraph\">More on the application in <a href=\"https:\/\/www.savioclima.com\/en\/2026\/09\/09\/axial-fans-for-genset-cooling-natural-gas-generator-applications\/\">Axial fans for genset cooling<\/a> and <a href=\"https:\/\/www.savioclima.com\/en\/2026\/10\/07\/data-center-fans-where-they-are-needed-and-how-to-choose-them\/\">Data center fans: where they are needed and how to choose them<\/a>.<\/p>\n\n<div class=\"wp-block-group cta-preventivo is-layout-flow wp-block-group-is-layout-flow\" style=\"background-color:#043751;padding:30px\">\n<h3 class=\"wp-block-heading\" style=\"color:#ffffff\">Send us your operating point<\/h3>\n\n<p class=\"wp-block-paragraph\" style=\"color:#ccddea\">Airflow, static pressure, ambient and altitude: our engineers will reply with a 60 Hz selection and a quote.<\/p>\n\n<div class=\"wp-block-buttons is-layout-flex wp-block-buttons-is-layout-flex\">\n<div class=\"wp-block-button\"><a class=\"wp-block-button__link has-text-color has-background\" href=\"https:\/\/www.savioclima.com\/en\/axial-fans-usa-canada\/#richiesta-offerta\" style=\"border-radius:4px;background-color:#ffffff;color:#043751\"><strong>Request 60 Hz data<\/strong><\/a><\/div>\n<\/div>\n<\/div>\n","protected":false},"excerpt":{"rendered":"<p>How to size genset radiator fans in US units: heat rejection, CFM, density correction for temperature and altitude, static pressure, and what changes on 60 Hz.<\/p>\n","protected":false},"author":5,"featured_media":835,"comment_status":"closed","ping_status":"","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[140],"tags":[],"class_list":["post-4338","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-news"],"aioseo_notices":[],"aioseo_head":"\n\t\t<!-- All in One SEO 4.9.9 - aioseo.com -->\n\t<meta name=\"description\" content=\"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.\" \/>\n\t<meta name=\"robots\" content=\"max-image-preview:large\" \/>\n\t<meta name=\"author\" content=\"gianluca\"\/>\n\t<link rel=\"canonical\" href=\"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/\" \/>\n\t<meta name=\"generator\" content=\"All in One SEO (AIOSEO) 4.9.9\" \/>\n\t\t<meta property=\"og:locale\" content=\"en_US\" \/>\n\t\t<meta property=\"og:site_name\" content=\"Savio Clima - Industrial Fans and Blowers\" \/>\n\t\t<meta property=\"og:type\" content=\"article\" \/>\n\t\t<meta property=\"og:title\" content=\"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO\" \/>\n\t\t<meta property=\"og:description\" content=\"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.\" \/>\n\t\t<meta property=\"og:url\" content=\"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/\" \/>\n\t\t<meta property=\"og:image\" content=\"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg\" \/>\n\t\t<meta property=\"og:image:secure_url\" content=\"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg\" \/>\n\t\t<meta property=\"og:image:width\" content=\"442\" \/>\n\t\t<meta property=\"og:image:height\" content=\"106\" \/>\n\t\t<meta property=\"article:published_time\" content=\"2026-10-22T15:54:00+00:00\" \/>\n\t\t<meta property=\"article:modified_time\" content=\"2026-10-23T09:21:29+00:00\" \/>\n\t\t<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n\t\t<meta name=\"twitter:title\" content=\"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO\" \/>\n\t\t<meta name=\"twitter:description\" content=\"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.\" \/>\n\t\t<meta name=\"twitter:image\" content=\"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg\" \/>\n\t\t<script type=\"application\/ld+json\" class=\"aioseo-schema\">\n\t\t\t{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"BlogPosting\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#blogposting\",\"name\":\"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO\",\"headline\":\"Genset Radiator Fans: How to Size Airflow and Static Pressure\",\"author\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/author\\\/gianluca\\\/#author\"},\"publisher\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/#organization\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.savioclima.com\\\/wp-content\\\/uploads\\\/2023\\\/10\\\/savio-clima-SPMD.jpg\",\"width\":1200,\"height\":980,\"caption\":\"Ventilatori assiali Savio Clima\"},\"datePublished\":\"2026-10-22T15:54:00+00:00\",\"dateModified\":\"2026-10-23T09:21:29+00:00\",\"inLanguage\":\"en-US\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#webpage\"},\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#webpage\"},\"articleSection\":\"News\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#breadcrumblist\",\"itemListElement\":[{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/#listItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/category\\\/news\\\/#listItem\",\"name\":\"News\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/category\\\/news\\\/#listItem\",\"position\":2,\"name\":\"News\",\"item\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/category\\\/news\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#listItem\",\"name\":\"Genset Radiator Fans: How to Size Airflow and Static Pressure\"},\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/#listItem\",\"name\":\"Home\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#listItem\",\"position\":3,\"name\":\"Genset Radiator Fans: How to Size Airflow and Static Pressure\",\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/category\\\/news\\\/#listItem\",\"name\":\"News\"}}]},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/#organization\",\"name\":\"Savio Clima\",\"description\":\"Industrial Fans and Blowers\",\"url\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/\",\"email\":\"savio@savioclima.it\",\"telephone\":\"+390119591601\",\"foundingDate\":\"1945-06-23\",\"logo\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.savioclima.com\\\/wp-content\\\/uploads\\\/2023\\\/09\\\/logo-savio-clima.png\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#organizationLogo\",\"width\":442,\"height\":106},\"image\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#organizationLogo\"},\"sameAs\":[\"https:\\\/\\\/www.linkedin.com\\\/company\\\/savioclima\\\/?originalSubdomain=it\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/author\\\/gianluca\\\/#author\",\"url\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/author\\\/gianluca\\\/\",\"name\":\"gianluca\",\"image\":{\"@type\":\"ImageObject\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#authorImage\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/0b4aef697e0ed98c2e153ef6be86002196bb80efd3f39a9536664e89cd20c154?s=96&d=mm&r=g\",\"width\":96,\"height\":96,\"caption\":\"gianluca\"}},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#webpage\",\"url\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/\",\"name\":\"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO\",\"description\":\"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.\",\"inLanguage\":\"en-US\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/#website\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#breadcrumblist\"},\"author\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/author\\\/gianluca\\\/#author\"},\"creator\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/author\\\/gianluca\\\/#author\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.savioclima.com\\\/wp-content\\\/uploads\\\/2023\\\/10\\\/savio-clima-SPMD.jpg\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#mainImage\",\"width\":1200,\"height\":980,\"caption\":\"Ventilatori assiali Savio Clima\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/2026\\\/10\\\/22\\\/genset-radiator-fan-sizing\\\/#mainImage\"},\"datePublished\":\"2026-10-22T15:54:00+00:00\",\"dateModified\":\"2026-10-23T09:21:29+00:00\"},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/#website\",\"url\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/\",\"name\":\"Savio Clima\",\"description\":\"Industrial Fans and Blowers\",\"inLanguage\":\"en-US\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.savioclima.com\\\/en\\\/#organization\"}}]}\n\t\t<\/script>\n\t\t<!-- All in One SEO -->\n\n","aioseo_head_json":{"title":"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO","description":"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.","canonical_url":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/","robots":"max-image-preview:large","keywords":"","webmasterTools":{"miscellaneous":""},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"BlogPosting","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#blogposting","name":"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO","headline":"Genset Radiator Fans: How to Size Airflow and Static Pressure","author":{"@id":"https:\/\/www.savioclima.com\/en\/author\/gianluca\/#author"},"publisher":{"@id":"https:\/\/www.savioclima.com\/en\/#organization"},"image":{"@type":"ImageObject","url":"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg","width":1200,"height":980,"caption":"Ventilatori assiali Savio Clima"},"datePublished":"2026-10-22T15:54:00+00:00","dateModified":"2026-10-23T09:21:29+00:00","inLanguage":"en-US","mainEntityOfPage":{"@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#webpage"},"isPartOf":{"@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#webpage"},"articleSection":"News"},{"@type":"BreadcrumbList","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#breadcrumblist","itemListElement":[{"@type":"ListItem","@id":"https:\/\/www.savioclima.com\/en\/#listItem","position":1,"name":"Home","item":"https:\/\/www.savioclima.com\/en\/","nextItem":{"@type":"ListItem","@id":"https:\/\/www.savioclima.com\/en\/category\/news\/#listItem","name":"News"}},{"@type":"ListItem","@id":"https:\/\/www.savioclima.com\/en\/category\/news\/#listItem","position":2,"name":"News","item":"https:\/\/www.savioclima.com\/en\/category\/news\/","nextItem":{"@type":"ListItem","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#listItem","name":"Genset Radiator Fans: How to Size Airflow and Static Pressure"},"previousItem":{"@type":"ListItem","@id":"https:\/\/www.savioclima.com\/en\/#listItem","name":"Home"}},{"@type":"ListItem","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#listItem","position":3,"name":"Genset Radiator Fans: How to Size Airflow and Static Pressure","previousItem":{"@type":"ListItem","@id":"https:\/\/www.savioclima.com\/en\/category\/news\/#listItem","name":"News"}}]},{"@type":"Organization","@id":"https:\/\/www.savioclima.com\/en\/#organization","name":"Savio Clima","description":"Industrial Fans and Blowers","url":"https:\/\/www.savioclima.com\/en\/","email":"savio@savioclima.it","telephone":"+390119591601","foundingDate":"1945-06-23","logo":{"@type":"ImageObject","url":"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/09\/logo-savio-clima.png","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#organizationLogo","width":442,"height":106},"image":{"@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#organizationLogo"},"sameAs":["https:\/\/www.linkedin.com\/company\/savioclima\/?originalSubdomain=it"]},{"@type":"Person","@id":"https:\/\/www.savioclima.com\/en\/author\/gianluca\/#author","url":"https:\/\/www.savioclima.com\/en\/author\/gianluca\/","name":"gianluca","image":{"@type":"ImageObject","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#authorImage","url":"https:\/\/secure.gravatar.com\/avatar\/0b4aef697e0ed98c2e153ef6be86002196bb80efd3f39a9536664e89cd20c154?s=96&d=mm&r=g","width":96,"height":96,"caption":"gianluca"}},{"@type":"WebPage","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#webpage","url":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/","name":"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO","description":"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.","inLanguage":"en-US","isPartOf":{"@id":"https:\/\/www.savioclima.com\/en\/#website"},"breadcrumb":{"@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#breadcrumblist"},"author":{"@id":"https:\/\/www.savioclima.com\/en\/author\/gianluca\/#author"},"creator":{"@id":"https:\/\/www.savioclima.com\/en\/author\/gianluca\/#author"},"image":{"@type":"ImageObject","url":"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg","@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#mainImage","width":1200,"height":980,"caption":"Ventilatori assiali Savio Clima"},"primaryImageOfPage":{"@id":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/#mainImage"},"datePublished":"2026-10-22T15:54:00+00:00","dateModified":"2026-10-23T09:21:29+00:00"},{"@type":"WebSite","@id":"https:\/\/www.savioclima.com\/en\/#website","url":"https:\/\/www.savioclima.com\/en\/","name":"Savio Clima","description":"Industrial Fans and Blowers","inLanguage":"en-US","publisher":{"@id":"https:\/\/www.savioclima.com\/en\/#organization"}}]},"og:locale":"en_US","og:site_name":"Savio Clima - Industrial Fans and Blowers","og:type":"article","og:title":"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO","og:description":"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.","og:url":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/","og:image":"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg","og:image:secure_url":"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg","og:image:width":"442","og:image:height":"106","article:published_time":"2026-10-22T15:54:00+00:00","article:modified_time":"2026-10-23T09:21:29+00:00","twitter:card":"summary_large_image","twitter:title":"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO","twitter:description":"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.","twitter:image":"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg"},"aioseo_meta_data":{"post_id":"4338","title":"Genset Radiator Fan Sizing: CFM and Static Pressure | SAVIO","description":"How to size radiator cooling fans for generator sets: heat rejection to CFM, temperature and altitude correction, static pressure in in. w.g., and 60 Hz fan laws.","keywords":null,"keyphrases":null,"primary_term":null,"canonical_url":null,"og_title":null,"og_description":null,"og_object_type":"default","og_image_type":"featured","og_image_url":"https:\/\/www.savioclima.com\/wp-content\/uploads\/2023\/10\/savio-clima-SPMD.jpg","og_image_width":"442","og_image_height":"106","og_image_custom_url":null,"og_image_custom_fields":null,"og_video":"","og_custom_url":null,"og_article_section":null,"og_article_tags":null,"twitter_use_og":true,"twitter_card":"default","twitter_image_type":"default","twitter_image_url":null,"twitter_image_custom_url":null,"twitter_image_custom_fields":null,"twitter_title":null,"twitter_description":null,"schema":{"blockGraphs":[],"customGraphs":[],"default":{"data":{"Article":[],"Course":[],"Dataset":[],"FAQPage":[],"Movie":[],"Person":[],"Product":[],"ProductReview":[],"Car":[],"Recipe":[],"Service":[],"SoftwareApplication":[],"WebPage":[]},"graphName":"","isEnabled":true},"graphs":[]},"schema_type":"default","schema_type_options":null,"pillar_content":false,"robots_default":true,"robots_noindex":false,"robots_noarchive":false,"robots_nosnippet":false,"robots_nofollow":false,"robots_noimageindex":false,"robots_noodp":false,"robots_notranslate":false,"robots_max_snippet":null,"robots_max_videopreview":null,"robots_max_imagepreview":"large","priority":0,"frequency":"default","local_seo":null,"limit_modified_date":false,"created":"2026-10-22 15:42:01","updated":"2026-10-23 09:21:31","ai":null,"breadcrumb_settings":null,"seo_analyzer_scan_date":null},"aioseo_breadcrumb":"<div class=\"aioseo-breadcrumbs\"><span class=\"aioseo-breadcrumb\">\n\t\t\t<a href=\"https:\/\/www.savioclima.com\/en\/\" title=\"Home\">Home<\/a>\n\t\t<\/span><span class=\"aioseo-breadcrumb-separator\">&raquo;<\/span><span class=\"aioseo-breadcrumb\">\n\t\t\t<a href=\"https:\/\/www.savioclima.com\/en\/category\/news\/\" title=\"News\">News<\/a>\n\t\t<\/span><span class=\"aioseo-breadcrumb-separator\">&raquo;<\/span><span class=\"aioseo-breadcrumb\">\n\t\t\tGenset Radiator Fans: How to Size Airflow and Static Pressure\n\t\t<\/span><\/div>","aioseo_breadcrumb_json":[{"label":"Home","link":"https:\/\/www.savioclima.com\/en\/"},{"label":"News","link":"https:\/\/www.savioclima.com\/en\/category\/news\/"},{"label":"Genset Radiator Fans: How to Size Airflow and Static Pressure","link":"https:\/\/www.savioclima.com\/en\/2026\/10\/22\/genset-radiator-fan-sizing\/"}],"_links":{"self":[{"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/posts\/4338","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/users\/5"}],"replies":[{"embeddable":true,"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/comments?post=4338"}],"version-history":[{"count":3,"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/posts\/4338\/revisions"}],"predecessor-version":[{"id":4346,"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/posts\/4338\/revisions\/4346"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/media\/835"}],"wp:attachment":[{"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/media?parent=4338"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/categories?post=4338"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.savioclima.com\/en\/wp-json\/wp\/v2\/tags?post=4338"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}